Installation position of fire door

Installation position of fire door

When the fireproof door is opened, the door leaf crosses the deformation joint, which may cause the door to close loosely and pose a risk of fire. During acceptance, on-site simulation is required to initiate testing:


1. Measurement tool: Use a laser marking instrument to detect the opening trajectory of the door leaf, ensuring a distance of ≥ 50mm from the deformation joint;


2. Structural review: Verify the position of deformation joints in the drawings and the installation coordinates of fire doors to avoid design conflicts;


3. Dynamic verification: Repeatedly open and close the door leaf, observe whether there is any jamming or deviation, and focus on checking the firmness of the hinge installation.


Common problem: Some projects aim to compress installation space for aesthetic purposes, and special attention should be paid to hidden dangers in the decoration renovation project.